Question 1
A 45 kVA, 480V primary, single-phase transformer has a primary FLC of 93.75A. At 125%, the calculated OCPD is 117.2A. What is the correct standard size primary OCPD?
Show answer & explanation
Correct answer: C - 125 amperes
10 free, exam-style Journeyman Electrician License Exam (JE) practice questions with answers and explanations. No signup required. Work through them below, then take the full free JE practice test to study every exam domain.
These 10 free JE questions are organized by exam domain, so you can see how each part of the Journeyman Electrician License Exam blueprint is tested. Reveal the answer and explanation under each question.
A 45 kVA, 480V primary, single-phase transformer has a primary FLC of 93.75A. At 125%, the calculated OCPD is 117.2A. What is the correct standard size primary OCPD?
Correct answer: C - 125 amperes
How many neutral-to-ground bonding points are permitted for a separately derived system?
Correct answer: B - One bonding point only
A dwelling has a total general lighting, small-appliance, and laundry load of 10,500 VA. After applying Table 220.42 demand factors, the demand load is:
Correct answer: A - 3,000 + (7,500 × 0.35) = 5,625 VA
A dwelling has one range rated at 14 kW. Using Table 220.55, the demand load is calculated as:
Correct answer: B - 8 kW × 1.10 = 8.8 kW
Using VD = 2KID/CM, what is the maximum one-way distance for a 120V, 20A circuit on 12 AWG copper (K=12.9, CM=6,530) with a 3% voltage drop limit (3.6V)?
Correct answer: B - 91 feet
A motor nameplate reads: 10 HP, 460V, 3-phase, FLA 13.5A, SF 1.15. For conductor sizing, the electrician uses:
Correct answer: B - 14A from Table 430.250
Three motors on a common feeder: 20 HP (27A), 10 HP (14A), and 5 HP (7.6A), all 460V, 3-phase. The minimum feeder conductor ampacity is:
Correct answer: B - 55.35 amperes
Can the next standard size rule (240.4(B)) be used to round up to a 25A breaker for 14 AWG copper (15A ampacity)?
Correct answer: B - No, 240.4(D) limits 14 AWG to 15A maximum and overrides 240.4(B)
A fire pump service must NOT have a disconnecting means that can be opened:
Correct answer: C - Automatically (such as by overcurrent or ground fault)
A PV module has an Isc of 9.5 amperes. The minimum conductor ampacity for the PV source circuit is closest to:
Correct answer: C - 14.8 amperes